Correction Procedures; Changing And Setting The Password; Identifying Ied Application Problems; Inspecting The Wiring - ABB Relion 650 Series Commissioning Manual

Busbar protection version 1.1 iec
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 9
Troubleshooting
Table 5:
Warning indication
Time Synch Error
BATTERY1 Error
Settings Changed
Setting Groups Changed
9.3

Correction procedures

9.3.1

Changing and setting the password

The password can only be set with PCM600.
9.3.2

Identifying IED application problems

Navigate to the appropriate menu in the LHMI to identify possible problems.
Check that the function is on.
Check that the correct setting group (1 to 4) is activated.
Check the blocking.
Check the mode.
Check the measurement value.
Check the connection to trip and disturbance recorder functions.
Check the channel settings.
9.3.2.1

Inspecting the wiring

The physical inspection of wiring connections often reveals the wrong connection for phase
currents or voltages. However, even though the phase current or voltage connections to IED
terminals might be correct, wrong polarity of one or more measurement transformers can
cause problems.
Check the current or voltage measurements and their phase information from Main
menu/Measurements/Analog primary values or Analog secondary voltages.
Check that the phase information and phase shift between phases is correct.
Correct the wiring if needed.
Check the actual state of the connected binary inputs.
62
Additional indications
For more information, see PCM600 documentation.
Change the parameter
3PhaseAnalogGroup/1:SMAI_20_n (n= the number of the SMAI used).
Changing the
special skills.
In PCM600, change the parameter
input) under the parameter settings for each current input.
© Copyright 2011 ABB. All rights reserved
Additional information
Source of the time synchronization is lost or time
system has made a time reset.
Auxiliary power is disconnected.
Settings have been changed.
Setting group has been changed.
Negation in Configuration/Analog modules/
Negation parameter is not recommended without
CTStarPointn (n= the number on the current
1MRK 505 264-UEN A
GUID-D3FA85BA-1E36-4F8B-BD71-85C7AC46A0B4 v1
GUID-D8E1AECF-1FD8-4996-A447-948B52EAD0C2 v5
GUID-665B75A6-A074-4A03-ADF1-3D0FAD198E61 v2
Busbar protection REB650
Commissioning manual