Selecting The Test Mode; Testing The Digital I/O Interface - ABB Relion 615 Series Operation Manual

Ansi
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 8
Commissioning
8.5.1
8.5.2
144

Selecting the test mode

The test mode can be activated using the LHMI. The green Normal LED is flashing to
indicate that the test mode is activated.By default, the test mode can only be changed from
the LHMI. Activation by remote client is possible, see the technical manual.
The Normal LED also flashes if the protection relay detects a diagnostic
failure. Check the test mode setting and the protection relay's IRF alarm
contact status to find the reason for the failure.
The test mode is useful for simulated testing of functions and outputs without providing
current inputs.
1.
Select Main menu/Tests/IED test/Test mode and press
A071154-ANSI V2 EN
Figure 94:
Entering test mode
2.
Select the test mode status with
3.
Press
to confirm the selection.
If the test mode is not cancelled, it remains on and the Normal LED
remains flashing.

Testing the digital I/O interface

To activate or deactivate, for example, a digital output:
or
.
1MAC054853-MB B
.
615 series ANSI
Operation Manual

Advertisement

Table of Contents
loading

Table of Contents