ABB Relion 615 Series Operation Manual page 122

Ansi
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 7
Troubleshooting
114
Table 19:
Warning indications and codes
Warning indication
Warning code
Warning
Watchdog reset
Warning
Power down det.
Warning
IEC61850 error
Warning
Modbus error
Warning
DNP3 error
Warning
Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning
Logic error
Warning
SMT logic error
Warning
GOOSE input error
ACT error
Warning
GOOSE Rx. error
Warning
AFL error
Warning
SMV config error
Warning
Comm. channel down
Warning
Unack card comp.
Warning
Protection comm.
Warning
ARC1 cont. light
Warning
ARC2 cont. light
Table continues on next page
Additional information
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has dropped
too low.
20
Error when building the IEC 61850 data
model.
21
Error in the Modbus communication.
22
Error in the DNP3 communication.
24
Error in the Data set(s).
25
Error in the Report control block(s).
26
Error in the GOOSE control block(s).
27
Error in the SCL configuration file or the file
is missing.
28
Too many connections in the
configuration.
29
Error in the SMT connections.
30
Error in the GOOSE connections.
31
Error in the ACT connections.
32
Error in the GOOSE message receiving.
33
Analog channel configuration error.
34
Error in the SMV configuration.
35
Redundant Ethernet (HSR/PRP)
communication interrupted.
40
A new composition has not been
acknowledged/accepted.
50
Error in protection communication.
85
A continuous light has been detected on
the ARC light input 1.
86
A continuous light has been detected on
the ARC light input 2.
1MAC054853-MB B
615 series ANSI
Operation Manual