Section 8
Commissioning
8.4.2.3
8.4.2.4
8.4.2.5
134
Table 25:
Link status
Parameter
Link status

Defining Ethernet port settings

Change the Ethernet port settings primarily via PCM600 to ensure that
PCM600 is able to export a consistent configuration to SYS600. Ethernet
port settings are recommended to be changed only when the device is
stand-alone and properly configured.
1.
Select Main menu/Configuration/Communication/Ethernet/Rear port.
2.
Define the settings for the Ethernet port.
IP address
Subnet mask
Default gateway of the optional rear port Ethernet connector

Defining serial port settings

The serial COM setting is not currently supported.
1.
Select Main menu/Configuration/Communication/COM1 or COM2.
2.
Define the settings for the serial port.
It is possible to change the general serial communication parameters per port. Select
fiber or galvanic mode with the proper baud rate, parity and delays depending on the
system architecture and the selected physical communication port.

Setting communication protocol parameters

1.
Select Main menu/Configuration/Communication/<protocol>.
2.
Change the protocol specific settings.
Possible settings to be changed are, for example, the selected communication port,
address and link mode.
Function
Link status in write direction: By writing 1 to the
parameter the diagnostic counters are reset to 0.
Link status in monitoring direction: If the driver is in
use by any communication protocol, the monitoring
value shows 1. In other case, the value is 0.
1MAC054853-MB B
615 series ANSI
Operation Manual