Parameter Descriptions
VLT
14-22 Operation Mode
Option:
Function:
14-22 Operation Mode also reverts to default
setting [0] Normal Operation.
14-26 Action at Inverter Fault
Option:
Function:
[0]
Trip
When the frequency converter detects an over-
4
4
voltage, it will trip immediately.
NOTE
It is recommended to choose [0] Trip in
hoisting applications.
[1]
Warning When the frequency converter detects an over-
*
voltage, it will give warning immediately. After
protection filter, it will trip.
NOTE
It is recommended to disable protection
mode in hoisting applications.
4.11.4 15-4* Drive Identification
Parameters containing read only information about the
hardware and software configuration of the frequency
converter.
14-41 AEO Minimum Magnetization
Range:
Function:
66%
[40-75%] Enter the minimum allowable magnetization
*
for AEO. Selecting a low value reduces energy
loss in the motor, but may also reduce
resistance to sudden load changes.