Parameter Descriptions
VLT
4.5.3 4-4* Adjustable Warnings 2
4-40 Warning Frequency Low
Range:
Function:
0.00
[0.0 Hz-
Use this parameter to set a lower limit
Hz
Depend on the
for the frequency range.
*
value of 4-41
When the motor speed falls below this
Warning
limit, the display reads SPEED LOW.
4
4
Frequency High]
Warning bit 10 is set in 16-94 Ext.
Status Word. Output Relay can be
configured to indicate this warning.
LCP warning light does not light when
this parameter set limit is reached.
4-41 Warning Frequency High
Range:
Function:
400.0
[Depend on
Use this parameter to set a higher
Hz
the value of
limit for the frequency range.
*
4-40 Warning
When the motor speed exceeds this
Frequency Low
limit, the display reads SPEED HIGH.
-400.0 Hz]
Warning bit 9 is set in 16-94 Ext.
Status Word. Output Relay can be
configured to indicate this warning.
LCP warning light does not light
when this parameter set limit is
reached.
4.5.4 4-5* Adjustable Warnings
Parameter group containing adjustable warning limits for
current, speed, reference and feedback.
Warnings are shown in display, programmed output or
serial bus.
4-50 Warning Current Low
Range:
Function:
Use this parameter to set a lower limit
for the current range.
If current drops below the set limit,
warning bit 8 is set in 16-94 Ext. Status
Word.
Output Relay can be configured to
indicate this warning. LCP warning light
does not light when this parameter's set
limit is reached.
0.00
[0.00-26.00
Set value for low current limit.
A
A]
*
26
MG02C602 - VLT
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx
®
Micro Drive FC 51 Programming Guide
4-51 Warning Current High
Range:
Function:
Use this parameter to set an upper limit
for the current range.
If current exceeds the set limit, warning
bit 7 is set in 16-94 Ext. Status Word.
Output Relay can be configured to
indicate this warning. LCP warning light
does not light when this parameter's
set limit is reached.
26.00
[0.00-26.00
Set upper current limit.
A
A]
*
4-54 Warning Reference Low
Range:
Function:
-4999.000
*
[-4999.000-
Use this parameter to set a lower
Depend on the
limit for the reference range.
value of 4-55
When the actual reference falls
Warning
below this limit, the display reads
Reference High]
Reference Low. Warning bit 20 is
set in 16-94 Ext. Status Word.
Output Relay can be configured to
indicate this warning. LCP warning
light does not light when this
parameter set limit is reached.
®