Parameter Descriptions
VLT

4.6 Parameter Group 5: Digital In/Out

4.6.1 5-** Digital In/Out
The following describes all digital input command
functions and signals.
4.6.2 5-1* Digital Inputs
4
4
Parameters for configuring the functions for the input
terminals.
The digital inputs are used for selecting various functions
in the frequency converter. All digital inputs can be set to
the following:
[0]
No Operation
The frequency converter will not react to
signals transmitted to the terminal.
[1]
Reset
Reset the frequency converter after a Trip/
Alarm. Not all alarms can be reset.
[2 ] Coast Inverse
Coasting stop, inverted input (NC). The
frequency converter leaves the motor in free
mode.
[3]
Coast and
Reset and coasting stop inverted input (NC).
reset inv.
The frequency converter resets and leaves
the motor in free mode.
[4]
Quick stop
Inverted input (NC). Generates a stop in
inverse
accordance with the quick-stop ramp time
set in 3-81 Quick Stop Ramp Time. When
motor stops, shaft is in free mode.
[5]
DC-brake inv.
Inverted input for DC braking (NC). Stops
motor by energizing it with DC current for a
certain time period, see 2-01 DC Brake
Current. Function is only active when value
in 2-02 DC-Braking Time is different from 0.
[6]
Stop inv.
Stop inverted function. Generates stop
function when selected terminal goes from
logical level "1" to "0". Stop is performed
according to selected ramp time.
[8]
Start
Select start for a start/stop command.
1 = Start, 0 = stop.
[9]
Latched start
Motor starts if a pulse is applied for min. 2
ms. Motor stops when Stop inverse is
activated.
[10] Reversing
Change direction of motor shaft rotation.
Reversing signal only changes direction of
rotation; it does not activate start function.
Select [2] Both directions in 4.10 Motor Speed
Direction.
0 = normal, 1 = reversing.
[11] Start
Use for start/stop and for reversing at the
reversing
same time. Signals on start [8] are not
allowed at the same time.
0 = stop, 1 = start reversing.
[12] Enable start
Use if motor shaft must rotate clockwise at
forward
start.
28
MG02C602 - VLT
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx
®
Micro Drive FC 51 Programming Guide
[13] Enable start
Use if motor shaft must rotate counter-
reverse
clockwise at start.
[14] Jog
Use for activating jog speed. See 3-11 Jog
Speed.
[16] Preset
Preset reference bit 0, 1 and 2 enables a
reference bit
choice between one of the eight preset
0
references according to below.
[17] Preset
Same as preset reference bit 0 [16], see 3-10
reference bit
Preset Reference.
1
[18] Preset
Same as preset reference bit 0 [16].
reference bit
2
[19] Freeze
Freeze actual reference. The frozen reference
reference
is now the point of enable/condition for
Speed up and Speed down to be used. If
Speed up/down is used, speed change
always follows ramp 2 (3-51 Ramp2 Ramp-up
Time and 3-52 Ramp2 Ramp-down Time) in
the range 3-02 Minimum Reference - 3-03
Maximum Reference.
[20] Freeze output Freeze the actual motor frequency (Hz). The
frozen motor frequency is now the point of
enable/condition for Speed up and Speed
down to be used. If Speed up/down is used,
the speed change always follows ramp 2 in
the range 4-12 Motor Speed Low Limit - 4-14
Motor Speed High Limit.
NOTE
When freeze output is active, the
frequency converter cannot be stopped
via a low [8] Start signal. Stop the
frequency converter via a terminal
programmed for Coasting Inverse [2] or
Coast and reset, inverse [3].
[21] Speed up
Select Speed up and Speed down if digital
control of the up/down speed is desired
(motor potentiometer). Activate this function
by selecting either Freeze reference or
Freeze output. When Speed-up is activated
for less than 400 ms. the resulting reference
will be increased by 0.1%. If Speed-up is
activated for more than 400 ms. the
resulting reference will ramp according to
ramp 2 in 3-51 Ramp2 Ramp-up Time.
[22] Speed down
Same as Speed-up [21].
[23] Setup select
Set 0-10 Active set-up to Multi set-up.
bit 0
Logic 0 = set up 1, Logic 1 = Set up 2.
[26] Precise stop
Prolong the stop signal to give a precise
inverse (only
stop independent of scan time. The function
terminal 33)
is available for terminal 33 only.
[27] Start, precise
As [26], but including Start.
stop (only
terminal 33)
®