Parameter Descriptions
VLT
4.2.7 1-9* Motor Temperature
With an estimated motor temperature monitor the
frequency converter is able to estimate motor temperature
without having a thermistor mounted. It is thus possible to
receive a warning or an alarm, if motor temperature
exceeds upper operational limit.
1-90 Motor Thermal Protection
4
4
Option:
Function:
Using ETR (Electronic Terminal Relay) the
motor temperature is calculated based on
frequency, speed and time. Danfoss
recommends using The ETR function, if a
thermistor is not present.
NOTE
ETRElectronic Overload calculation is
based on motor data from parameter
group 1-2* Motor Data.
[0]
No Protection Disables temperature monitoring.
*
[1]
Thermistor
A thermistor connected to either digital or
Warning
analog input gives a warning if upper limit
of motor temperature range is exceeded,
(see 1-93 Thermistor Resource).
[2]
Thermistor
A thermistor connected to either digital or
Trip
analog input gives an alarm and makes the
frequency converter trip if upper limit of
motor temperature range is exceeded, (see
1-93 Thermistor Resource.
[3]
ETR Warning
If calculated upper limit of motor
temperature range is exceeded, a warning
occurs.
[4]
ETR Trip
If 90% of calculated upper limit of motor
temperature range is exceeded, an alarm
occurs and the frequency converter trips.
NOTE
When the ETR function has been selected the drive will
store the recorded temperature at power down and this
temperature will resume at power up regardless of the
elapsed time. Changing 1-90 Motor Thermal Protection back
to [0] No Protection will reset the recorded temperature.
18
MG02C602 - VLT
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx
®
Micro Drive FC 51 Programming Guide
1-93 Thermistor Resource
Option:
Function:
Select the thermistor input terminal.
[0]
*
None
No thermistor is connected.
[1]
Analog
Connect thermistor to analog input terminal
Input 53
53.
NOTE
Analog input 53 cannot be selected for
other purposes when selected as
thermistor resource.
[6]
Digital
Connect thermistor to digital input terminal 29.
input 29
While this input functions as thermistor input,
it will not respond to the function chosen in
5-13 Digital Input 29. The value of 5-13 Digital
Input 29 remains however unchanged in
parameter database while function is inactive.
Input Digital/
Supply
Analog
Voltage
Digital
10 V
Analog
10 V
Table 4.1
®
is a registered Danfoss trademark
Threshold Cut-
out
Values
<800 Ω ⇒ 2.9
kohm
<800 Ω ⇒ 2.9
kohm