Diagnostics Of The Cfu; Executing Diagnostics Of The Cfu; Diagnostics Via Led Displays - Siemens Simatic CFU Commissioning Manual

Distributed i/o compact field unit
Hide thumbs Also See for Simatic CFU:
Table of Contents

Advertisement

Diagnostics of the CFU

9.1

Executing diagnostics of the CFU

A wide range of information and tools are available for diagnosing the status of the CFU.
Diagnostic possibilities
● Displays
Some LED displays are located on the front of the CFU. This provides you with an overview
of the status of the CFU. You can find information about this in section "Diagnostics via
LED displays (Page 91)".
● Tools
Information about the most important tools for diagnosing PCS 7 systems is available in
the Service Manual PCS 7 Process Control System; Service support and diagnostics
(www.siemens.com/pcs7-documentation).
– Maintenance Station
– Module information
– Connection status
– Inventory data
– Status of field devices and bus lines
9.2

Diagnostics via LED displays

Below, you will find tables containing information on the status and error messages of the
Compact Field Unit.
SIMATIC CFU
Commissioning Manual, 07/2018, A5E39252870-AC
With the Maintenance Station, PCS 7 offers you the possibility to call up information
about the status of all the PCS 7 components in hierarchically structured diagnostics
screens. For this, the data of a component is analyzed with the existing online functions
of the associated tools. You can access the ES data from the diagnostics screens (can
be controlled via access protection mechanisms).
Select the CFU in HW Config.
Select menu command PLC > Module information.
Call from Start menu Siemens SIMATIC programs: STEP 7 > NCM S7 > Diagnostics
Callup via SIEMENS SIMATIC program: SIMATIC > SIMATIC Management Console
(license required) > Plant view > shortcut menu command "Determine inventory data"
Call via SIMATIC PDM
The CFU PA does not undertake any detailed diagnostics of field devices and bus
cables. The detail diagnostics is possible, in as far as the required device descriptions
are available in suitable programs (for example SIMATIC PDM).
Open SIMATIC PDM > Device > CFU <V...> Configuration.