Commissioning

8.3 Commissioning (overview of procedure)

8.3
Commissioning (overview of procedure)
Procedure
Offline commissioning with project
Advantag‐
Engineering is possible without hardware.
es
You perform the commissioning in conclusion.
Procedure 1. CFU: Configuring (Page 86)
2. Optional (If you perform this step, step 8 can be
omitted)
Topology: Configuring (Page 62)
If you configure the topology, this enables
automatic name assignment on device
replacement in PCS 7 systems through use of
neighborhood relationships.
3. Freely configurable channels: Configuring
(Page 68) and assigning parameters (Page 78)
4. Field devices: Configuring (Page 71)
5. Compile the configuration.
6. Establish the online connection to the automation
system.
7. Download the configuration to the automation
system.
8. Assigning device name (Page 60)
9. LED status: Checking (Page 91)
If necessary, open the module information in order
to receive more precise diagnostic information.
10. Optional:
CFU: Assigning parameters via SIMATIC PDM
(Page 84)
11. CFU PA field devices: Assigning parameters via
SIMATIC PDM (Page 86)
Result
All steps up to step 6 can be performed without hard‐
ware.
Commissioning is performed starting from step 7.
54
Online commissioning with
project
Fast commissioning
through efficient determina‐
tion of devices present in
the system and direct as‐
signment of parameters in
the system
1. Online: Assigning
device name (Page 60)
2. CFU: Configuring
(Page 67)
3. Optional:
Topology Configuring
(Page 62)
If you configure the
topology, this enables
automatic name
assignment on device
replacement in PCS 7
systems through use of
neighborhood
relationships.
4. Using a wizard for CFU
configuration (Page 55)
5. Read back IOs
(Page 86)
Assigning parameters
for freely configurable
channels
6. Optional:
CFU: Assigning
parameters via
SIMATIC PDM
(Page 84)
7. CFU PA field devices:
Assigning parameters
via SIMATIC PDM
(Page 84)
Commissioning Manual, 07/2018, A5E39252870-AC
PDM stand alone with‐
out project
Advance commissioning
with real devices and cor‐
rect parameters without
a project in PCS 7 or
STEP 7
1. Online: Assigning
device name
(Page 63)
2. Process devices
network view:
Creating networks
and inserting a CFU
(Page 89)
3. Using a wizard for
CFU configuration
(Page 55)
4. Read back IOs
(Page 86)
5. CFU PA field
devices:
Assigning
parameters via
SIMATIC PDM
(Page 86)
● CFU and field device
parameters are
assigned.
● CFU is not linked to
any project.