Configuring With Pdm Stand Alone - Siemens Simatic CFU Commissioning Manual

Distributed i/o compact field unit
Hide thumbs Also See for Simatic CFU:
Table of Contents

Advertisement

Additional information
● Section "Using a wizard for CFU configuration (Page 55)"
● Section ""Expert Functions" dialog (Page 59)"
● Section "Displaying DPV0 alarms on CFU LEDs (Page 82)"
● Section "Re-reading field device data or restarting the field device (Page 105)"
8.9

Configuring with PDM Stand alone

Creating a network
1. Open the process device network view in SIMATIC Manager.
2. In the left-hand window, select the "Networks" folder in the tree view, and select the shortcut
menu command Insert New Object > Object.
The "Insert Object" dialog opens.
3. Click the "Assign Device Type" button.
Inserting the CFU
Follow the steps below to insert objects one at a time in higher-level objects.
Higher level object
"Networks" folder
"Communication network" folder
PROFINET network
1. In the right-hand window, select the higher-level object in the tree structure.
2. Select the shortcut menu command Insert New Object > Object.
The "<Insert ... SIMATIC PDM Object(s)" dialog opens.
3. Enter the name of the tag in the opened dialog.
Note
The address of the CFU that you set in the "Insert SIMATIC PDM Object(s)" dialog can be
changed later on the "Communication" tab of the "Object properties" dialog.
SIMATIC CFU
Commissioning Manual, 07/2018, A5E39252870-AC
8.9 Configuring with PDM Stand alone
Object to be inserted
Communication network
Type of network over which the CFU is connected to the automa‐
tion system:
PROFINET > PROFINET networks > PROFINET network
CFU
Enter the following parameters in the dialog window:
● Object name
● IP address
Commissioning
89