Commissioning
8.5 Preparing the CFU for commissioning
8.5.3

Configuring the topology

Automatic name assignment during device replacement is possible in PCS 7 systems.
The automatic name assignment is only possible if the topology is configured. The downloaded
topology enables the required device name for a replacement device to be determined and
set based on neighborhood relationships on the PROFINET IO system.
Requirement
All components on the PROFINET IO system are created in HW Config.
Procedure
1. Select the PROFINET IO system to which the CFU is connected.
2. Select the menu command Edit > PROFINET IO > Topology.
The "Topology Editor" dialog box opens.
3. Select the "Graphic view" tab.
62
Commissioning Manual, 07/2018, A5E39252870-AC