5.2.3
Resetting the HWBB State
The following examples use the Σ-7W SERVOPACK with MECHATROLINK-III commands. If you
use a Σ-7C SERVOPACK, you will need to use Controller Section commands instead of MECHA-
TROLINK-III commands.
Important
Normally, after the SV_OFF (Servo OFF: 32 hex) command is received and power is no longer
supplied to the Servomotor, the /HWBB1 and /HWBB2 signals will turn OFF and the SERVO-
PACK will enter the HWBB state. If you turn ON the /HWBB1 and /HWBB2 signals in this state,
the SERVOPACK will enter a base block (BB) state and will be ready to acknowledge the
SV_ON (Servo ON: 31 hex) command.
/HWBB1
/HWBB2
MECHATROLINK-III
command for axi A
V_ON command
tatu for axi A
E TP command
input ignal
monitor for axi A
ERVOPACK
tatu for axi A
MECHATROLINK-III
command for axi B
V_ON command
tatu for axi B
E TP command
input ignal
monitor for axi B
ERVOPACK
tatu for axi B
OFF
(motor current hut-OFF reque t)
MON command
and other command
0
1
HWBB tate
MON command
and other command
0
1
HWBB tate
ON
(normal operation)
0
0
BB tate
Operating tate
V_ON
command
0
1
0
0
BB tate
Operating tate
5.2 HWBB Function
5.2.3 Resetting the HWBB State
V_ON
command
1
0
5
5-7