8.3 Starting maintenance

Pressurized parts
Overview
Establishing the de-
pressurized status
HON 380 gas pressure regulator with HON 673/674 controller
Risk of serious injury posed by pressurized components moving in an uncon-
trolled manner when handled improperly.
If not handled properly or in the event of a defect, gas can escape from pressur-
ized components under high pressure and cause serious injuries and even death.
Before you start working on these components:
 Close all connections leading to the gas-carrying line.
 Establish a depressurized status. Residual amounts of energy must be depres-
surized as well.
Schematic diagram using the RE1 DN50 and HON 673 as a reference:
The numbers have the following meaning:
No.
Meaning
1
Inlet stop valve armature
2
Gas pressure regulator
3
Pressure gauge
4
Outlet stop valve armature
5
Valve for blowdown line
6
Blowdown line
Proceed as follows:
Step
Description
1
Close the outlet stop valve armature (4).
2
Close the inlet stop valve armature (1).
3
Depressurize the gas pressure regulator.
4
Open the ball valve (5) in the blowdown line (6) to discharge the pressure be-
tween the inlet and the outlet valves.
Maintenance