EC-Smart-Vue: Humidity display
This input is used to display the Allure EC-Smart-Vue humidity reading if an Allure EC-Smart-Vue
equipped with a humidity option is connected to the system.
ID
nvoComSensor01_04
EC-Smart-Vue: Temperature display
This input is used to display the Allure EC-Smart-Vue temperature reading if an Allure EC-Smart-Vue
is connected to the system.
ID
nvoComSensor01_04
EC-Smart-Vue: CO
This input is used to display the Allure EC-Smart-Vue CO
Smart-Vue equipped with a CO
ID
nvoComSensor01_04
ECL-PTU-207 Preloaded Applications
Units
Percent Relative Humidity (%
RH)
Units
Degrees-Celsius (°C)
display
2
sensor is connected to the system.
2
Units
ppm
Valid Range
0 to 100 %RH
Valid Range
0 to 50°C
concentration reading if an Allure EC-
2
Valid Range
0 to 2000 ppm
Variables
Default Value
NaN
Default Value
NaN
Default Value
NaN