Chapter 2 Part Names - Mitsubishi Electric NZ2GN2B1-32D User Manual

Programmable controller cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2B1-32D:
Table of Contents

Advertisement

2
PART NAMES
This section describes part names of the I/O module.
• Spring clamp terminal block type
(1)
(6)
(7)
(8)
• Screw terminal block type
(1)
(6)
(7)
(8)
No.
Name
(1)
PW LED
RUN LED
ERR. LED
P1 LINK LED
P2 LINK LED
*3
DATA LINK LED
(2)
IP address setting switch
(3)
Function setting switch
(2)
(3)
(4)
(8)
(2)
(3)
(4)
(8)
Application
Indicates the power supply status of the I/O module.
On: Power supply ON
Off: Power supply OFF
Indicates the operating status of the I/O module.
On: Operating normally.
Flashing: Operating in unit test mode
Off: A major error has occurred.
Indicates the error status of the I/O module.
On: A moderate error or major error has occurred.
Flashing: A minor error has occurred.
Off: Operating normally.
Indicates the link status for P1.
On: Link-up
Off: Linkdown in progress
Indicates the link status for P2.
On: Link-up
Off: Linkdown in progress
Indicates the data link status of the I/O module.
On: Cyclic transmission being performed
Flashing: Cyclic transmission stopped
Off: Disconnected
Sets the fourth octet of the IP address.
Page 58 IP address setting switch setting
Sets functions of the I/O module.
Page 60 Function setting switch setting
(5)
(9)
(5)
(9)
2
2 PART NAMES
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents