6.5
Wiring of Terminal Block for Module Power Supply
and FG
Tightening torque
Tighten the terminal block mounting screws within the following specified torque range.
Tightening the screws too much may damage the I/O module case.
Screw type
Terminal block mounting screw (M2.5 screw)
Wire to be used
The following table describes the wire to be connected to the terminal block for module power supply and FG.
Diameter
22 to 16 AWG
Applicable solderless terminal
The following table lists the applicable solderless terminal.
Product
Terminal shape
name
Bar solderless
Ferrule (with insulation
terminal
sleeve)
Ferrule (without
insulation sleeve)
Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screws with a flathead screwdriver.
To install the terminal block, tighten the terminal block mounting screw with a flathead screwdriver.
Failure to secure the terminal block may cause drop, short circuit, or malfunction.
Type
Material
Stranded
Copper
Model
TE0.5-8, TE0.5-10
TE0.75-8, TE0.75-10
AI0.34-10TQ
AI0.5-10WH
AI0.75-10GY
A0.5-10
A0.75-10
A1.0-10
A1.5-10
Tightening torque range
0.2 to 0.3 N⋅m
Temperature rating
75 or more
Applicable wire
Bar solderless
size
terminal tool
0.3 to 0.5
NH-79A
0.75
0.34
CRIMPFOX6
0.5
0.75
0.5
0.75
1.0
1.5

6.5 Wiring of Terminal Block for Module Power Supply and FG