Setting item list
Item
RX Setting, RY Setting
Points
Start
End
RWr Setting, RWw Setting
Points
Start
End
Network Synchronous Communication
For the RX/RY setting and the RWw/RWr setting, set a value in the corresponding setting range. If a value
outside the setting range is set, an error occurs on the "Network Diagnostics" window.
Description
Set the assignment of RX/RY points in units of 16 points.
The RX/RY start number is displayed.
The RX/RY end number is displayed.
Set the assignment of RWw/RWr points in units of 4 points.
The RWw/RWr start number is displayed.
The RWw/RWr end number is displayed.
Set "Asynchronous" for the I/O module.
Setting range
0 to 32 (Default value: 32)
0 to 144 (Default value: 4)
• Asynchronous (Default value)
• Synchronous
7 PARAMETER SETTING