Setting procedure
Operating procedure
1.
Create a project.
[Project]
[New...]
2.
For "CPU Parameter" in "Link Direct Device Setting", set "Extended Mode (iQ-R Series Mode)".
[CPU Parameter]
When writing the module parameters of the RJ71GN11-T2 to the CPU module with the engineering tool, set
"Extended Mode (iQ-R Series Mode)" for "Link Direct Device Setting".
When "Q Series Compatible Mode" is set for "Link Direct Device Setting", "Write to PLC" cannot be executed.
3.
Set the master/local module in the following window.
[Navigation window]
9 PROGRAMMING
84
9.2 Program Example
[Memory/Device Setting]
[Parameter]
[Module Information]
[Link Direct Device Setting]
Right-click
[Link Direct Device Setting]
[Add New Module]