Programming With #93 Menu Mode

NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should
be programmed via Device programming.
After programming all system related programming fields in the usual way, press #93 while still in programming mode to
display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu
selection. Pressing 0 will display the next choice in sequence.
NOTE: All references in this manual for number of zones, user codes, partitions, VistaKey modules, the master
partition and the event log capacity, use the VISTA-128FB's features. See page 2 for the table listing the differences
between the VISTA-32FB and the VISTA-128FB control panels. All other features are identical for both panels.
U L
For UL installations, verify that the audio alarm verification feature is disabled.
#93 MENU MODE KEY COMMANDS
The following is a list of commands used while in the menu mode.
#93
Enters Menu mode
[4]
Serves as ENTER key. Press to have keypad accept entry.
[#]
Backs up to previous screen.
0
Press to answer NO
1
Press to answer YES
001-009
All data entries are either 2-digit or 3-digit entries.
000
Exits menu mode, back into field programming mode, when entered at the first question for each category.
Menu selections are as follows:
PROMPT
ZONE PROG?
1 = YES
0 = NO
0
EXPERT MODE?
1 = YES
0 = NO
0
REPORT CODE PROG?
1 = YES
0 = NO
0
ALPHA PROG?
1 = YES
0 = NO
0
DEVICE PROG?
1 = YES
0 = NO
0
EXPLANATION
For programming the following:
Zone Number
Zone Response Type
Partition Number for Zone
Dialer report code for zone
Input Device Type for zone (whether RF, polling loop, etc.)
Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.
Zone Attributes (e.g., Arm w/Fault, Silent, etc.)
Same as Zone Programming except:
Done with a minimum number of keystrokes.
Can program wireless keys using pre-defined templates.
NOTE: Be aware some of the zone attributes cannot be programmed in the Expert Mode. These can only be
done in Zone Programming.
For programming the following:
Alarm report codes for zones
Restore & supervisory codes
All other system report codes
For entering alpha descriptors for the following:
Zone Descriptors
Installer's Message
Custom Words
Partition Descriptors
Relay Descriptors
For defining the following device characteristics for addressable devices, including keypads, RF receivers
(5881), output relay modules (4204/4204CF), FSA modules, 4285/4286 VIP Module, ECP Long Range Radio
(7820), Panel Link module, and VISTA gateway module:
Device Address
Device Type
Keypad Options (incl. partition assignment)
RF House ID
LRR Options (incl. programming radio)
– 12 –