5.10 Mimic display driver FT2001-A1
Building Technologies
Fire Safety
The mimic display driver FT2001-A1 is a parallel LED indication for the system-
wide signaling of events and is connected to the FDnet detector line. It has 48
LEDs that are installed on a ground plan panel.
FDnet
1
FT2001
2
DC/AC
Figure 9: Integration of the mimic display driver into the fire detection installation
1
Mimic display driver
2
Optional external DC or AC supply
Guidelines
●
External power supply is possible with DC or AC.
●
Mimic display drivers that are not fed by the ↑ detector line (separate power
supply) must be electrically isolated from the system voltage.
●
Several floor repeater terminals and floor repeater displays, which are
connected to the same ↑ line card, must not be operated via an electrically
connected supply.
NOTICE
Influencing the earth fault monitoring
Faults
●
Electrical isolation of the supply unit must be present for devices on the FDnet
that are fed separately (with the exception of the transponder).
●
When an external supply unit is used, it must be taken into account that should
the external supply unit fail, the ↑ maximum current connection factor
increases significantly (line failure is possible).
●
When power supply is ensured via the detector line, the high maximum current
connection factor (MK) must be taken into account.
●
A maximum of 20 mimic display drivers can be connected per fire control
panel.
Project planning of indication and operation devices
Mimic display driver FT2001-A1
5
49 | 242