Siemens FS20 Planning Manual page 44

Fire detection system
Table of Contents

Advertisement

Project planning of indication and operation devices
5
Floor repeater terminal FT2010 and floor repeater display FT2011
44 | 242
Building Technologies
Fire Safety
Guideline
External power supply is possible with DC or AC.
↑ Floor repeater terminals and ↑ floor repeater displays that are not fed by the
↑ detector line (separate power supply) must be electrically isolated from the
system voltage.
NOTICE
Influencing the earth fault monitoring
Faults
Electrical isolation of the supply unit must be present for devices on the FDnet
that are fed separately (with the exception of the transponder).
When an external supply unit is used, it must be taken into account that should
the external supply unit fail, the ↑ maximum current connection factor
increases significantly (line failure is possible).
When power supply is ensured via the detector line, the high maximum current
connection factor must be taken into account.
Several floor repeater terminals and floor repeater displays, which are
connected to the same ↑ line card, must not be operated via an electrically
connected supply.
Only a maximum of eight floor repeater terminals and floor repeater displays
can be connected per FDnet line driver (a line card has one ↑ line driver
featuring two loops) on fire control panels. This results in the following options:
Fire control panel FC2020 supports a total of eight floor repeater terminals
and floor repeater displays.
Fire control panel FC2030 supports a total of 24 floor repeater terminals
and floor repeater displays.
Fire control panel FC2040 supports a total of 16 floor repeater terminals
and floor repeater displays.
Fire control panel FC2060, without extra line cards (FDnet/C-NET),
supports a total of 16 floor repeater terminals and floor repeater displays.
Fire control panel FC2060, supplemented by five extra line cards (FDnet/C-
NET), supports a maximum total of 50 floor repeater terminals and floor
repeater displays.
Fire control panel FC2080, which can be equipped with a maximum of 30
line cards (FDnet/C-NET), supports a maximum total of 50 floor repeater
terminals and floor repeater displays.
Floor repeater terminals and floor repeater displays are system-wide
configurable.
A maximum of five ↑ stations can be configured with system-wide ↑ visibility
on the FDnet.
All other floor repeater terminals and floor repeater displays have visibility to a
maximum of two other stations.
008843_v_en_--
2015-12-15