11 Determining the compact stations

11.1 Determining additional compact station components

Use
Extra FDnet lines
Connecting collective
detectors
Connecting MS9i detectors ●
Connecting AnalogPLUS
detectors
Connecting interactive
detectors
Connecting interactive Ex
detectors
Additional programmable
inputs/outputs
Building Technologies
Fire Safety
The planning steps in this chapter apply to the compact ↑ stations and must be
performed separately for each station used of type FC2020, FC2030, FC2040,
FC2060, and FT2040.
You will find the planning of the FC2080 in a separate chapter.
You will find information about the country-specific availability of devices in
document 'Delivery Release'.
See also
2 Assembling the FC2080 [➙ 170]
Use the information in this chapter to determine the options for the individual
compact stations, FC2020, FC2030, FC2040, and FC2060. These details are
required to determine the power supply and batteries.
Required components
↑ Loop extension (FDnet) FCI2003-A1 The loop extension is used on the
↑ Line card (FDnet/C-NET) FCL2001-
A1
Input/output module FDCIO223 for
connecting collective lines on the
FDnet
Line card (collective) FCL2002-A1
Line card (MS9i) FCL2003-A1
Line card (AnalogPLUS) FCL2005-A1
Line card (interactive) FCL2006-A1
Line card (interactive Ex) FCL2007-A1
I/O card (programmable) FCI2008-A1
Input/output modules FDCIO221,
FDCIO223, FDCIO224, FDCI221
Determining the compact stations
Determining additional compact station components
Notes
periphery board.
The line card (FDnet/C-NET) is used
in the card cage and can be used in
the fire control panel FC2060.
The input/output module FDCIO223
is connected on the FDnet line.
The line card (collective) is used in
the card cage and can be used in the
fire control panels FC2030 and
FC2060.
The line card (MS9i) is used in the
card cage and can be used in the fire
control panels FC2030 and FC2060.
The line card (AnalogPLUS) is used
in the card cage and can be used in
the fire control panels FC2030 and
FC2060.
The line card (interactive) is used in
the card cage and can be used in the
fire control panels FC2030 and
FC2060.
The line card (interactive Ex) is used
in the card cage and can be used in
the fire control panels FC2030 and
FC2060.
The I/O card is used in the card cage
and can be used in the fire control
panels FC2030 and FC2060.