Planning The Fire Brigade Periphery [De] - Siemens FS20 Planning Manual

Fire detection system
Table of Contents

Advertisement

Assembling the FC2080
12

Planning the fire brigade periphery [DE]

12.6 Planning the fire brigade periphery [DE]
FC2080
FCC2002-A1
FCI2007-A1
FDnet
FCL2001-A1
180 | 242
Building Technologies
Fire Safety
In the fire control panel FC2080, the fire brigade periphery [DE] cannot be
connected via the fire brigade periphery module. These connections must be
established using I/O cards or I/O modules. Additionally, a key safe adapter is
required to ensure the fire brigade key depot works correctly. The simplified
diagrams below show the connection options for the fire brigade periphery [DE] in
the FC2080.
Connection via I/O module FDCIO224
RT fire active/confirmed
FDCIO224
Figure 70: Simplified connection diagram for FBF and FSD via I/O module in FC2080
FCC2002-A1 Processor unit (19", FC2080)
FCI2007-A1 I/O card (RT)
FCL2001-A1 ↑ Line card (FDnet/C-NET)
FDCIO224 I/O module
SDA Key safe adapter SDA3000 [DE]
FBF Fire brigade operating panel [DE]
FAT Fire brigade indication panel [DE]
↑ ÜE/FSE Release element zone/release element [DE]
FSD Fire brigade key depot [DE]
RS485
Sabotage input
RT fire active
Heating active
SDA
FBF
FAT
ÜE/
FSE
FSD
008843_v_en_--
2015-12-15