Siemens FS20 Planning Manual page 36

Fire detection system
Table of Contents

Advertisement

Project planning of indication and operation devices
5
Operation and indication devices
36 | 242
Building Technologies
Fire Safety
With the exception of the 19" pedestal housing on the FC2080, the fire terminal
board FTI2001 must be installed for power distribution. When it is installed in the
FC2080, the fire terminal (Touch) is supplied with power by the processor unit via
the adapter supplied with the FC2080 and the associated flat cable.
Integrated operation and indication devices
The integrated operation and indication devices are installed in the standard
operating terminal as an option or on a country-specific basis.
LED indicator (internal) FTO2002-A1 (24 LEDs red & yellow)
LED module FTO2008-A1 (24 LEDs red/green & yellow)
Event printer FTO2001-A1
EVAC-NL operating unit FTO2007-N1 [NL]
Operating add-on (2xEVAC term.) FCM2008-N1 [NL]
FBA terminal FTO2004-C1 [CH]
Remote operation and indication devices
Remote operating and indication devices are installed decentrally.
↑ Floor repeater terminal FT2010-A1, FT2010-C1
↑ Floor repeater display FT2011-A1
Mimic display driver FT2001-A1
Mimic display driver (EVAC) FT2003-N1
Fire brigade operating panel (FBF) [DE]
Fire brigade operation and indication panel (FAT) [DE] / [AT]
Telecommunications system via ESPA-4.4.4 interface
Event printer Fujitsu DL3750+
PC-based operation and indication
PC-based operation is a software-based, remote indication and operating unit.
SintesoView FXS2009-A1
↑ Management stations: MM8000 Danger Management System, GMA
Manager [DE], DESIGO
Optional operation and indication with the 19" station FC2080
The fire control panel (19", modular) FC2080 does not have an integrated
operating unit. Optionally, an operating unit and a maximum of two operating add-
ons can be installed in the door. The optional operating unit and the operating add-
ons form one separate, independent ↑ station. The connection from the operating
terminal to the FC2080 is established as follows:
External supply from the processor unit (19", FC2080) via a flat cable to the
operating unit
Signal and data exchange from the processor unit (19", FC2080) via
↑ FCnet/SAFEDLINK
INSIGHT
TM
008843_v_en_--
2015-12-15