Item no. Designation/function
1
↑ 'GAP' station and
↑ Router station
2
↑ SAFEDLINK stations
3
Router station
4
Standby router stations
5
↑ Ethernet station and
'Secondary GAP'
6
SAFEDLINK sub-net 1
7
FCnet/LAN
8
SAFEDLINK sub-net 2
9
Ethernet switch
(modular) FN2012
10
Ethernet connection
11
↑ Management station
12
Firewall
13
Management station via
'Secondary GAP'
Building Technologies
Fire Safety
Ethernet
address(es)
192.168.201.1
192.168.100.1
192.168.100.x
Any
10.169.29.82
192.168.100.2
10.169.29.80
10.169.30.01
Table 31: External access to extended network via GAP
Planning the networking of the stations
Remote access to the extended network with GAP
↑ SAFEDLINK
Notes
address
Configured as GAP with DHCP
server function and router function
192.168.1.x
IP address range for SAFEDLINK
sub-net 1 (pre-setting, can be
changed)
IP address range for Ethernet sub-
net (pre-setting, can be changed)
192.168.2.x
IP address range for SAFEDLINK
sub-net 2 (pre-setting, can be
changed)
Address must not be the same as
the address in the FCnet/LAN
Connected to Ethernet switch
(modular) of the standby station
(example)
Ethernet participants from external
sub-net (sample address),
connected to firewall
Sample addresses
Sample address
8
125 | 242
008843_v_en_--
2015-12-15