Siemens SITRANS F Series Operating Instructions Manual page 253

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
10240
Float / 4
10242
Float / 4
10268
Float / 4
10270
Float / 4
9408
Float / 4
9592
Unsigned / 2
9481
Unsigned / 2
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD
Parameter
Description
Upper range
Upper process viscosi‐
value viscosity
ty value that is mapped
to the upper nominal
range boundary selec‐
ted by Frequency value
high (9435). Applicable
if Process value (9404)
= 21 or 29.
Lower range
Lower process viscosi‐
value viscosity
ty value that is mapped
to the lower nominal
range boundary selec‐
ted by Frequency value
low (9437). Applicable
if Process value (9404)
= 21 or 29.
Upper range
Upper rate of change
value ROC
value that is mapped to
the upper nominal
range boundary selec‐
ted by Frequency value
high (9435). Applicable
if Process value (9404)
= 36.
Lower range
Lower rate of change
value ROC
value that is mapped to
the lower nominal
range boundary selec‐
ted by Frequency value
low (9437). Applicable
if Process value (9404)
= 36.
Damping filter
Time constant of damp‐
ing filter for frequency
output signal.
Fail-safe activa‐
Fail-safe activation con‐
tion condition
dition.
Fail-safe min.
Minimum time the out‐
time
put stays in fail-safe be‐
havior.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units register)
1.0
-
[m²/s]
(7524)
0.0
-
[m²/s]
(7524)
1.0
-
[m/s²]
(8564)
0.0
-
[m/s²]
(8564)
0.0
0.0 - 100.0
[s]
1
● 0: Bad status of
selected process
value
● 1: Active
Maintenance alarm
or Failure (NAMUR)
0
0 - 100
[s]
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
253