Siemens SITRANS F Series Operating Instructions Manual page 112

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

Diagnostics and troubleshooting
9.8 Fault codes and corrective actions
ID/
Diagnostic
Icons
185
CH2
186
CH3
187
CH3
188
CH3
189
CH4
190
CH4
191
CH4
195
CH2
196
CH2
112
Action
External failure. Connected sensor or output to
input channel is out of operation range. Please
check connected sensor or output source.
Input current too low. Check wiring and signal of
connected sensor or output source to input
channel
Input current too high. Check wiring and signal
of connected sensor or output source to input
channel
External failure. Connected sensor or output to
input channel is out of operation range. Please
check connected sensor or output source.
Input current too low. Check wiring and signal of
connected sensor or output source to input
channel
Input current too high. Check wiring and signal
of connected sensor or output source to input
channel
External failure. Connected sensor or output to
input channel is out of operation range. Please
check connected sensor or output source.
Loop current in lower saturation. Check proc‐
ess conditions or align limit to normal operation.
Adjust channel 2 parameter 'Lower range value'
Loop current in upper saturation. Check proc‐
ess conditions or align limit to normal operation.
Adjust channel 2 parameter 'Upper range value'
Comment
If Operation mode is config‐
ured to Current input
If Operation mode is config‐
ured to Current input
If Operation mode is config‐
ured to Current input
If Operation mode is config‐
ured to Current input
If Operation mode is config‐
ured to Current input
If Operation mode is config‐
ured to Current input
If Operation mode is config‐
ured to Current input
If Operation mode is config‐
ured to Current output
If Operation mode is config‐
ured to Current output
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fst030

Table of Contents