Siemens SITRANS F Series Operating Instructions Manual page 229

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
10128
Float / 4
10130
Float / 4
10132
Float / 4
10134
Float / 4
10136
Float / 4
10138
Float / 4
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD
Parameter
Description
Upper range
Upper process pres‐
value pressure
sure value that is map‐
ped to the upper nomi‐
nal range boundary se‐
lected by Frequency
value high (9235). Ap‐
plicable if Process val‐
ue (9204) = 20.
Lower range
Lower process pres‐
value pressure
sure value that is map‐
ped to the lower nomi‐
nal range boundary se‐
lected by Frequency
value low (9237). Appli‐
cable if Process value
(9204) = 20.
Upper range
Upper dimensionless
value dimen‐
value that is mapped to
sionless
the upper nominal
range boundary selec‐
ted by Frequency value
high (9235). Applicable
if Process value (9204)
= 28, 32, 33, 34, or 36.
Lower range
Lower dimensionless
value dimen‐
value that is mapped to
sionless
the lower nominal
range boundary selec‐
ted by Frequency value
low (9237). Applicable
if Process value (9204)
= 28, 32, 33, 34, or 36.
Upper range
Upper current value
value current
that is mapped to the
upper nominal range
boundary selected by
Frequency value high
(9235). Applicable if
Process value (9204) =
25 or 26.
Lower range
Lower current value
value current
that is mapped to the
lower nominal range
boundary selected by
Frequency value low
(9237). Applicable if
Process value (9204) =
25 or 26.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units register)
100000.0
-
[Pa]
(7548)
0.0
-
[Pa]
(7548)
1.0
-
0.0
-
20.0
-
[mA]
4.0
-
[mA]
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
229