Modbus
Data type /
register
Size in bytes
8403
Unsigned / 2
8404
Unsigned / 2
8416
Float / 4
8419
Unsigned / 2
8500
Float / 4
8503
Unsigned / 2
8504
Unsigned / 2
8516
Float / 4
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD
Parameter
Description
Totalizer 2 set
Run, reset, or preset to‐
talizer 2.
Possible selections:
Totalizer 2 di‐
Totalizer 2 direction.
rection
Totalizer 2 pre‐
Preset value which will
set value
be used when Totalizer
2 set is set to 2
Totalizer 2 tar‐
Sets the desired mode
get mode
for the totalizer.
Totalizer 3 value Totalized value of total‐
izer 3. Units depends
on the selected proc‐
ess value the totalizer
is configured to.
Write access if Totaliz‐
er 3 target mode is set
to 16: Manual
Totalizer 3 set
Run, reset, or preset to‐
talizer 3.
Totalizer 3 di‐
Totalizer 3 direction.
rection
Totalizer 3 pre‐
Preset value which will
set value
be used when Totalizer
3 set is set to 2
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units register)
0
● 0: Totalize
● 1: Reset
● 2: Preset to Totalizer
1 preset value
1
● 0: Balanced
● 1: Positive
● 2: Negative
● 3: Hold
-
-
(8321 / 8320 /
8322)
8
● 8. Auto, the totalizer
algorithm running
● 16: Man, the totalizer
algorithm is stopped.
The totalizer value
can be written
-
-
(8321 / 8320 /
8322)
0
● 0: Totalize
● 1: Reset
● 2: Preset to Totalizer
1 preset value
1
● 0: Balanced
● 1: Positive
● 2: Negative
● 3: Hold
-
-
(8321 / 8320 /
8322)
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
145