Modbus
Data type /
register
Size in bytes
8915
Float / 4
8917
Float / 4
8911
Float / 4
8913
Float / 4
8919
Float / 4
8921
Float / 4
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD
Parameter
Description
Upper range
Upper volume flow val‐
value volume
ue that is mapped to
flow
the upper nominal
range boundary selec‐
ted by Frequency value
high (8935). Applicable
if Process value (8904)
= 1.
Lower range
Lower volume flow val‐
value volume
ue that is mapped to
flow
the lower nominal
range boundary selec‐
ted by Frequency value
low (8937). Applicable
if Process value (8904)
= 1.
Upper range
Upper mass flow value
value mass flow
that is mapped to the
upper nominal range
boundary selected by
Frequency value high
(8935). Applicable if
Process value (8904) =
0.
Lower range
Lower mass flow value
value mass flow
that is mapped to the
lower nominal range
boundary selected by
Frequency value low
(8937). Applicable if
Process value (8904) =
0.
Upper range
Upper process density
value density
value that is mapped to
the upper nominal
range boundary selec‐
ted by Frequency value
high (8935). Applicable
if Process value (8904)
= 2.
Lower range
Lower process density
value density
value that is mapped to
the lower nominal
range boundary selec‐
ted by Frequency value
low (8937). Applicable
if Process value (8904)
= 2.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units register)
0.4 % • max.
-
volume flow
[m
/s]
3
(7500)
0.0
-
[m
/s]
3
(7500)
0.2 • max.
-
mass flow-
[kg/s]
(7400)
0.0
-
[kg/s]
(7400)
1600
-
[kg/m
]
3
(7600)
600
-
[kg/m
]
3
(7600)
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
209