Siemens SITRANS F Series Operating Instructions Manual page 223

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
9591
Unsigned / 2
9281
Unsigned / 2
9114
Unsigned / 2
9115
Float / 4
7153
Float / 4
9186
Float / 4
9188
Float / 4
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD
Parameter
Description
Filter-safe acti‐
Fail-safe activation con‐
vation condition
dition.
Fail-safe min.
Minimum time the out‐
time
put stays in fail-safe be‐
havior.
Fail-safe behav‐
Current output reaction
ior
in case of a fault.
Fail-safe value
Output value in case of
a fault and when Fail-
safe behavior (9114) is
configured to 4.
Forced value
Forced value when
forcing is active.
Offset adjust‐
Command to trim the
ment
lower range value of
the loop current.
Simulate a loop current
of 4.0 mA, measure the
current with an ampere
meter and write the
measured value to this
register.
Gain adjustment Command to trim the
upper range value of
the loop current.
Simulate a loop current
of 20.0 mA, measure
the current with an am‐
pere meter and write
the measured value to
this register.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units register)
1
● 0: Bad status of
selected process
value
● 1: Active
Maintenance alarm
or Failure (NAMUR)
0
0 - 100
[s]
0
● 0: Lower fault current
● 1: Upper fault current
● 2: Last valid value
● 3: Disabled
● 4: Custom value
0.0
0.0 - 25.0
[mA]
4.0
3.5 - 25.0
[mA]
-
0 - 25
-
0 - 25
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Write on‐
ly
Write on‐
ly
223