How to Programme

2 How to Programme
2
2
2.1 Programming with MCT-10 Setup
software
The frequency converter can be programmed from a PC via
RS-485 COM port by installing the MCT-10 Setup software.
This software can either be ordered using code number
130B1000 or downloaded from the Danfoss Web site: http://
www.danfoss.com/BusinessAreas/DrivesSolutions/Software-
download/ Please refer to manual MG.10.RX.YY.

2.2 Local Control Panel (LCP)

The following instructions are valid for the FC101 LCP. The
LCP is divided into four functional sections:
A. Alphanumeric display.
B. Menu key.
C. Navigation keys and indicator lights (LEDs).
D. Operation keys and indicator lights (LEDs).
1
2
3
4
6
10
7
8
9
A. Alpha Numeric Display
The LCD-display is back-lit with 2 alpha-numeric lines. All
data is displayed on the LCP.
12
1-20 Motor Power
A
[2] 0.12kW-0.16HP
Setup 1
Main
Status
Quick
B
Menu
Menu
Menu
Com
C
On
OK
Warn
Alarm
Hand
Off
Auto
D
On
Reset
13
14
MG.18.B1.02 - VLT
VLT HVAC Basic Drive Programming Guide
A number of information can be read from the display:
1
Parameter number and name.
2
Parameter value.
3
Set-up number shows the active set-up and the edit set-up.
If the same set-up acts as both active and edit set-up, only
that set-up number is shown (factory setting). When active
and edit set-up differ, both numbers are shown in the
display (Setup 12). The number flashing, indicates the edit
set-up.
4
Motor direction is shown to the bottom left of the display –
indicated by a small arrow pointing either clockwise or
counterclockwise.
5
The triangle indicates if the LCP is in status, quick menu or
main menu.
B. Menu Key
Use the menu key to select between status, quick menu or
main menu.
C. Navigation keys and indicator lights (LEDs)
6
Com led: Flashes when bus communication is communicating.
7
Green LED/On: Control section is working.
8
Yellow LED/Warn.: Indicates a warning.
9
Flashing Red LED/Alarm: Indicates an alarm.
10 [Back]: For moving to the previous step or layer in the
navigation structure
5
11 Arrows [
parameters and within parameters. Can also be used for
setting local reference.
12 [OK]: For selecting a parameter and for accepting changes to
11
parameter settings
12
D. Operation keys and indicator lights (LEDs)
11
13
[Hand on]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTE
On
Please note that terminal 27 Digital Input
(5-12 Terminal 27 Digital Input) has coast inverse as
default setting. This means that [Hand On] will not
15
start the motor if there is no 24V to terminal 27, so
please connect terminal 12 to terminal 27.
14
[Off/Reset]: Stops the motor (off). If in alarm mode the alarm
will be reset.
15
[Auto on]: Frequency converter is controlled either via control
terminals or serial communication.
®
is a registered Danfoss trademark
] [
]: For maneuvering between parameter groups,