How to Programme
At power up the user is
asked to choose hte
prefered laguage.
2
2
1
The next screen will be
the Wizard screen.
2
3
34
Setup 1
35
Setup 1
14
Select language
[1] English
Setup 1
Main
Status
Quick
Menu
Menu
Menu
OK
On
Warn
Alarm
O
Auto
Hand
Reset
On
On
Power Up Screen
OK
Press OK to start Wizard
Press Back to skip it
Setup 1
Status
Quick
Main
if
OK
Menu
Menu
Menu
OK
On
Warn
Alarm
O
Hand
Auto
Reset
On
On
Wizard Screen
if
0.0 Hz
0.0 kW
Setup 1
Main
Status
Quick
Menu
Menu
Menu
OK
On
Warn
Alarm
O
Auto
Hand
Reset
On
On
Status Screen
The Wizard can always be
reentered via the Quick Menu!
(Do not AMA)
Wizard completed
Auto Motor Tuning OK
33
Press OK to accept
Press OK
Setup 1
0.0 Hz
0.0 kW
MG.18.B1.02 - VLT
VLT HVAC Basic Drive Programming Guide
0-03 Regional Settings
[0] International
Setup 1
4-12 Motor Speed Low Limit
16
0000 Hz
Setup 1
4-14 Motor Speed High Limit
17
0000 Hz
Setup 1
3-41 Ramp 1 Ramp Up Time
18
0003 s
Setup 1
3-42 Ramp 1 Ramp Down Time
0003 s
19
Setup 1
1-73 Flying start
20
[0] Disable
Setup 1
6-19 Terminal 53 Mode
21
Current
[0] Current
Setup 1
6-12 Terminal 53 Low Current
4mA
24
Setup 1
6-13 Terminal 53 High Current
20mA
25
Setup 1
3-02 Minimum Reference
0 Hz
26
Setup 1
3-03 Maximum Reference
27
0050 Hz
Setup 1
5-40 Function Relay 1
[0] No function
28
Setup 1
5-40 Function Relay 2
29
[0] No function
Setup 1
1-29 Automatic Motor Adaption (AMA)
30
[0] O
Setup 1
AMA running
31
-----
Setup 1
AMA OK
®
is a registered Danfoss trademark
4
1-20 Motor Power
6
1.10 kW
Setup 1
1-22 Motor Voltage
400 V
7
Setup 1
1-23 Motor Frequency
8
0050 Hz
Setup 1
1-24 Motor Current
9
04.66 A
Setup 1
1-25 Motor Nominal Speed
10
1420 RPM
Setup 1
Select if Terminal 53 is used
for current or voltage input.
Voltage
6-10 Terminal 53 Low Voltage
0.07 V
22
Setup 1
6-11 Terminal 53 High Voltage
10 V
23
Setup 1
Please note that Terminal 27
Digital Input (par. 5-12) has coast
inverse as default setting. This means
that AMA cannot be performed if there
is no 24V to terminal 27 so please
connect terminal 12 to terminal 27.
Do AMA
AMA Failed
32
Setup 1
AMA failed
Need help?