How to Programme
Closed Loop Set-up Wizard
2
2
28
29
30
31
16
VLT HVAC Basic Drive Programming Guide
Current
6-22 Terminal 54 Low Current
4 mA
6-24 Terminal 54 Low Ref./Feedb. Value
Hz
0016
6-23 Terminal 54 High Current
20
mA
6-25 Terminal 54 High Ref./Feedb. Value
50
MG.18.B1.02 - VLT
0-03 Regional Settings
1
[0]
International
4-12 Motor speed low limit
13
0016
Hz
4-14 Motor speed high limit
14
0050
Hz
3-41 Ramp 1 ramp-up time
15
0003
s
3-42 Ramp1 ramp-down time
17
0003
s
1-73 Flying Start
18
[0]
No
20-00 Feedback1 source
18a
[2]
Analog in 54
3-02 Min Reference
20
[1]
0
3-03 Max Reference
21
[1]
50
3-10 Preset reference [0]
22
[1]
0
6-29 Terminal 54 Mode
[1]
Voltage mode
23
6-26
Terminal 54 Filter time constant
32
0,01
s
20-81 PI Normal/Inverse Control
33
[0]
Normal
20-83 PI Start Speed
34
0
Hz
20-93 PI Proportional Gain
35
0,01
s
20-94 PI Integral Time
36
9999
s
1-29 Automatic Motor Adaption
37
[1]
Enable
®
is a registered Danfoss trademark
Asynchronous Motor
1-20 Motor Power
3
1.10
kW
1-22 Motor Voltage
4
0050
V
1-23 Motor frequency
5
0050
Hz
1-24 Motor current
6
04.66
A
1-25 Motor nominal speed
7
1420
RPM
This dialog is forced to be set to
[2] Analog in 54
3-10 Preset reference is the set-point
Voltage
6-20 Terminal 54 Low Voltage
0,07
V
6-24 Terminal 54 Low Ref./Feedb. Value
0
Hz
6-21 Terminal 54 High Voltage
10
V
6-25 Terminal 54 High Ref./Feedb. Value
0050
Hz
Please note that Terminal 27 Digital Input (par. 5-12)
has coast inverse as default setting. This means that
AMA can not be performed if there is no 24V to terminal
27 so please connect terminal 12 to terminal 27.