3.3 Accessories
component
Configurable parity
Configurable interface
type
LED "Status"
(above the DIL switches,
only visible if the blue
cover is removed)
Table 3- 7
Pin
Enclosure
1
2
3
4
5
6
7
8
9
Modbus connection Sub-D
62
Function
You can set the parity using the software under
"P-INTERFACES/P-fieldbus/P-PB/PN/Modbus/P-Modbus RTU/parity".
If you enter a value of 0 under
"P-INTERFACES/P-fieldbus/P-PB/PN/Modbus/P-Modbus RTU/BUS-address" then the parity is
set by the hardware. Set the binary parity according to the following list:
00: not available
01: none (standard for RTU)
10: even
11: odd
Set this switch according to the interface you want to use.
0: RS 485
1: RS 232
Flashing red at different
frequencies
Flashing green at 1 Hz,
0.5 s On, 0.5 s Off
Flashing green at 2 Hz,
0.25 s On, 0.25 s Off
Pin assignment of the Modbus connection with Sub-D connector
Hardware error on the Modbus board: Contact the service de-
partment.
Initialization of the Modbus board OK
Initialization of the Modbus board has errors: Contact the service
department.
Designation
Shield
-
RS 232 - TX
RS 232 - RX
-
GND
+ 5 V
RS 485 D0
RS 485 D1
-
Installation and Operating Instructions SINAMICS G180
Function
Cable shield
Not used
Signal (transmit)
Signal (receive)
Not used
Signal ground
Supply voltage
-
-
Not used
Operating Instructions, 02/2019, 4BS0751-007