Operation
8.5 Special functions
Table 8- 9
Terminal / component
-K11
41, 42
U1,V1,W1
8
55
1 und 51
U2, V2, W2
8.5.2

Multiple function of the analog and digital inputs

Analog inputs 1 and 2
The analog inputs have several functions:
● Under "P-ANALOG INPUTS/Analog input 1/AI-function" you can set the value from
"Analog" to "PTC", "KTY84" or "PT100".
● Under "P-ANALOG INPUTS/Analog input 2/AI-function" you can set analog input 2 from
"Analog" to "PTC", "KTY84" or "PT100".
● Also adjust the corresponding DIL switches of the -S2 switch row on board CB08
● More detailed information can be found in the section "DIL switches S1 and S2
(Page 149)".
The following functions are now available:
● "Analog":
The analog input operates as a voltage input at control cable terminals -X2:52-51 / 54-51
or as a current input at control cable terminals -X2:50-51 / 53-51 The value is available as
"AI 1" or "AI 2" for further processing.
● "PTC":
The analog input operates as a PTC thermistor input at control cable terminals
-X2:50-51 / 53-51. The PTC thermistor state is available for further processing as
selection bit "PTC AI 1" or "PTC AI 2".
● "KTY84":
The analog input operates as a direct input for a KTY84-130 temperature sensor at
control cable terminals -X2:50-51 / 53-51. The measured temperature is available as an
analog value under "T-AI1" or "T-AI 2" for further processing.
● "PT100":
The analog input operates as a direct input for a PT100 temperature sensor at control
cable terminals -X2:50-51 / 53-51. The measured temperature is available as an analog
value under "T-AI1" or "T-AI 2" for further processing.
Any analog input can only be used for one function. It is not possible to use several functions
simultaneously for one input.
160
Motor contactor functions
Function
Output side main contactor
Design recommendation: AC3 current of the contactor is at least the inverter
output current
Digital output for the main contactor control
Mains connection
Main contactor feedback input
24 V DC supply voltage
Jumper for ground connection
Motor connection
Installation and Operating Instructions SINAMICS G180