8.3.2

Operation according to "NAMUR 1"

(D)
(S)
Figure 8-7
Control behavior for "test" (dynamic)
● Enter the command "Controller release" and "CTRL.OFF" using the <On> and <Off>
buttons on the display.
● Make the setpoint value setting using the <down arrow> and <up arrow> buttons.
● Reset errors by pressing the buttons <S+I> simultaneously. The locking and the OUT
input on the control cable terminal block reset the control.
Control behavior for "normal" (static)
● Control the operation of the controller release with a switch (NO) at -X2:10. Enter the
setpoint via control cable terminal block -X2 with analog setpoint value 1.
● When required use the reversing input (NO) -X2:16.
"Test" and "Normal" mode
● "Interlocking" (NC): The controller inhibit is activated if you open the contact at -X2:15.
The drive coasts to a stop and cannot be restarted. The inverter display shows the
message "Interlocking".
● "Off" (NC): You activate the controller inhibit if you remove the 24 V signal at -X2:11.
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
Dynamic: Pushbutton mode
Static: Switch mode
Assignment of the control cable terminals for "NAMUR 1" mode
Operation
8.3 NAMUR mode settings