● Use twisted pair cables for the same encoder tracks, e.g. A + / A -, B + / B -.
● Lay the cable shield on both sides at the encoder and inverter connector.
Connecting an HTL encoder at -X101
● Only use this encoder for field-oriented control with a speed accuracy < 1 %.
● Connect the encoder mechanically rigid to the motor.
● Do not place any gearbox between encoder and motor.
Figure 8-20
● In the case of making your own encoder cables, only lay the shield on the inverter side.
8.4.7

Connect the PC via USB at -X50B

Figure 8-21
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
HTL encoder at -X101
PC at -X50B via USB
8.4 Controlling the external connections of the inverter
Operation
153