11.1 Reading event log

11.1
Reading event log
If a fault occurs, the event log of the inverter stores the following data:
● Which error has occurred?
● With parallel-connected inverters:
In which system has the fault occurred?
● Data and time of the error event
● Various actual values such as, e.g. setpoint, motor current, motor voltage, motor
frequency etc.
These data are stored for the last 64 errors. The event number 01 is the most recent error.
Procedure
Read the event log using the "IMS" software.
You can also read these data on the display. Proceed as follows:
1. Press <I> and then the <down arrow> until "I-MEMORY" is shown on the screen.
2. Press <Return> to reach the first event, e.g. "I-Memory/01:Flt>Undervoltage".
If you press <Return> again, you can view all the data stored for this event.
3. Press <S> to return.
Read out all data of the last event using the software "IMS" before you contact the Service
Center for assistance with an error message. In this way, you significantly simplify the error
localization.