Derating

Derating
• Derating for ambient temperature
• Derating for air pressure
• Derating for low running speed
• Derating for installing long motor cables
or larger cable cross-section
Derating for ambient temperature
The ambient temperature (T
maximum temperature allowed. The aver-
age (T
) over 24 hours must be at
AMB,AVG
least 5 °C lower in accordance with VDE
160 5.2.1.1.
If the VLT
frequency converter is operated
®
at temperatures above 40 °C (45 °C in
CT), then a derating of the continuous out-
put current is necessary.
1. VLT
3002-08: IP 00 / IP 54
®
2. VLT
3002-08: IP 21 mounted with top fan.
®
VLT
3004 (200 V), 3006 (400 V, VT) and 3008 (400 / 500 V)
®
has a fan in IP 21 version, following curve 1.
1. VLT
3011-52: IP 20
®
2. VLT
3011-52: IP 54, VLT
®
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
) is the
AMB,MAX
3060-3250: IP 54; VLT
®
3032-3052, 230 V: IP 21 / IP54
®
131