Danfoss VLT 3000 Series Product Manual page 103

Frequency converter
Hide thumbs Also See for VLT 3000 Series:
Table of Contents

Advertisement

Parameter description
402
Binary input 18
(Input 18)
Value:
Start (start)
Pulse start (latch start)
No operation (no operation)
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
®
MG.30.A7.02 - VLT
is a registered Danfoss trademark
4.. Inputs and outputs
Function:
[0]
Used to select between different function
[1]
options for terminal 18. Start and stop will
[2]
take place according to the selected ramp
times in parameters 215 and 216.
Description of choices:
Start: Selected if a start/stop function is
required. Logic "1" = start, logic "0" =
stop.
Pulse start: To be selected if you want
start and stop function on 2 different
inputs (can be used with terminals 16, 17
or 27).
A pulse ("1" for minimum 20 msec) on
terminal 18 will start the motor.
A pulse ("0" for minimum 20 msec.) on
terminals 16, 17 or 27 will stop the motor.
No function: To be selected if you do not
want the frequency converter to react on
signals applied on terminal 18. When
using serial communication the input
status can be read and used by the
master.