M90S-4S User's Manual
Table 5-6: Setup-Pre-Alarm screen
Setting Item
Line Voltage Range
Line Frequency Range
Load
5.2.4 Information Screen
In INFORMATION menu, you can check the serial number, firmware versions, system configuration and settings of
the UPS. There are submenus under the INFORMATION, including Identification, System and Battery.
Xtreme Power Conversion Corporation
Sub Item
Explanation
Set line voltage range:
Upper limit
•
•
•
--
•
Lower limit
•
•
•
•
Set line frequency range:
Upper / Lower limit
•
--
•
•
•
Set UPS Overload percentage (40~100%)
•
--
Set UPS load unbalance percentage (20~100%)
•
Information menu
Figure 5-27 INFORMATION screen
+5%
+10%
+15%
+20% (Default)
-5%
-10%
-15%
-20% (Default)
+/- 1Hz
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
100% (Default)
100% (Default)
Uninterruptible Power Supply
Page 56