Xtreme Power Conversion M90S Series User & Installation Manual page 48

Online split-phase ups 6kva, 12kva, 18kva, 24kva models
Hide thumbs Also See for M90S Series:
Table of Contents

Advertisement

M90S-4S User's Manual
Table 5-3: Setup-General setting list
Setting Item
Sub Item
Model Name
Language
--
Adjust Time
System Installed Date
System Last Maintain
Date
TIME
Battery Installed Date
Battery Last Maintain
Date
Change
--
Password
Audible
Audible Mute
Alarm
Battery Mute
Fault Mute
Bypass Mute
Factory
--
Reset
EPO Function
Xtreme Power Conversion Corporation
Explanation
Enter UPS Name (xxxxxxxxxx).
The max. Length is 10 characters.
Provides 3 optional LCD languages:
English (Default)
Traditional Chinese
Simplified Chinese
Set current date and time.
(yyyy / mm / dd hour : min : sec)
MUST be set after UPS installation
Set system installed date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Set system latest maintenance date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Set battery installed date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Set battery latest maintenance date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Change
Password
It is to mute the buzzer when UPS in any mode.
Disable (Default)
Enable
It is to mute the buzzer when UPS in battery mode.
Disable (Default)
Enable
It is to mute the buzzer when UPS in fault mode.
Disable (Default)
Enable
It is to mute the buzzer when UPS in bypass mode.
Disable (Default)
Enable
Restore to factory default setting
Set EPO active status
Normal Close Active (Default)
Normal Open Active
Uninterruptible Power Supply
Page 48