Xtreme Power Conversion M90S Series User & Installation Manual page 52

Online split-phase ups 6kva, 12kva, 18kva, 24kva models
Hide thumbs Also See for M90S Series:
Table of Contents

Advertisement

M90S-4S User's Manual
--
Bypass
Mode
--
Converter
Mode
--
Battery
Mode Delay
Time
--
Cold Start
--
System
Shutdown
Time
--
Redundancy
Charger Test --
Xtreme Power Conversion Corporation
Uninterruptible Power Supply
Set bypass mode
Disable
Enable (Default)
MUST be reviewed after UPS instal-
lation.
If you need the Bypass power when
UPS is OFF, please enable it.
Set converter mode
Disable (Default)
Enable
Set Output Frequency
50Hz (Default)
60Hz
Set system shutdown delay time in
battery mode
(Disable or 10~990Min).
Disable (Default)
Not 0: Enable
When this feature is enabled, UPS
will shut off output after UPS oper-
ates in Battery mode for certain
seconds.
Set system shutdown time
(0.2~99min)
0.2 min (Default)
This delay time will start counting
when the
CONTROL-Shutdown Restore com-
mand is executed.
Set system restore time
(0~9999min)
1 min (Default)
This delay time will start counting
after shutdown time is elapsed
when the CONTROL-Shutdown
Restore command is executed.
Set redundancy
Redundancy: the QTY of redundant
UPS module(0~9)
0(Default)
MUST be set after UPS installation
Set charger test
Disable (Default)
Enable
Page 52