M90S-4S User's Manual
--
Bypass
Mode
--
Converter
Mode
--
Battery
Mode Delay
Time
--
Cold Start
--
System
Shutdown
Time
--
Redundancy
Charger Test --
Xtreme Power Conversion Corporation
Uninterruptible Power Supply
Set bypass mode
•
Disable
•
Enable (Default)
MUST be reviewed after UPS instal-
lation.
If you need the Bypass power when
UPS is OFF, please enable it.
Set converter mode
•
Disable (Default)
•
Enable
Set Output Frequency
•
50Hz (Default)
•
60Hz
Set system shutdown delay time in
battery mode
(Disable or 10~990Min).
•
Disable (Default)
•
Not 0: Enable
When this feature is enabled, UPS
will shut off output after UPS oper-
ates in Battery mode for certain
seconds.
Set system shutdown time
(0.2~99min)
•
0.2 min (Default)
This delay time will start counting
when the
CONTROL-Shutdown Restore com-
mand is executed.
Set system restore time
(0~9999min)
•
1 min (Default)
This delay time will start counting
after shutdown time is elapsed
when the CONTROL-Shutdown
Restore command is executed.
Set redundancy
Redundancy: the QTY of redundant
UPS module(0~9)
•
0(Default)
MUST be set after UPS installation
Set charger test
•
Disable (Default)
•
Enable
Page 52