Xtreme Power Conversion M90S Series User & Installation Manual page 51

Online split-phase ups 6kva, 12kva, 18kva, 24kva models
Hide thumbs Also See for M90S Series:
Table of Contents

Advertisement

M90S-4S User's Manual
Setup-System setting list is shown in Table 5-4.
Table 5-4: Setup-System setting list
Output
--
Voltage
ECO Voltage Range
ECO Setting
ECO Frequency Range
Bypass Voltage Range
Bypass
Setting
Bypass Frequency Range
ECO Mode
--
Xtreme Power Conversion Corporation
Uninterruptible Power Supply
Set output voltage
100Vac
110Vac
115Vac
120Vac(Default)
127Vac
MUST be reviewed after UPS
installation
Set ECO voltage range:
Upper Range
(Output Setting Voltage +6V) ~
(Output Setting
Voltage +12V)
(Output Setting Voltage +6V)
(Default)
Lower Range
(Output Setting Voltage -6V) ~
(Output Setting
Voltage -12V)
(Output Setting Voltage -6V)
(Default)
Set bypass Frequency range: Upper/
Lower limit
+/- 2Hz (Default)
+/- 3Hz
+/- 4Hz=
Set bypass voltage range:
Upper Range
(Output Setting Voltage +6V) ~
155V
140V (Default)
Lower Range
(Output Setting Voltage -6V) ~
88V
88V (Default)
Set bypass Frequency range:
Upper/ Lower limit
+/- 1Hz
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
Set ECO mode
Disable (Default)
Enable
Page 51