M90S-4S User's Manual
BATTERY TEST
Battery Age Alert
5.2.3 Pre-Alarm Screen
Use UP and DOWN buttons to switch different sub-menus. Press ENTER button to go into the Pre-Alarm setting
screen.
Pre-Alarm setting can be set in any operation mode. See Setup-Pre-Alarm setting list in Table 5-6.
Xtreme Power Conversion Corporation
Periodic Battery Test
Battery Test Interval
Battery Test Type
Battery Age Alert (Months)
Figure 5-25 Setup-Pre-Alarm screen
Uninterruptible Power Supply
Set periodic battery test disable or enable
Disable (Default)
Enable
Set battery test interval (7~99 Days)
30 Days (Default)
Set testing time for battery test (10~1000sec)
Short Time(10S) (Default)
Long Time(0.1M~0.9M)
Long Time(1M~99M)
Till Battery Low
Set battery age for replacement.
(Disable,12~60Months)
Disable (Default)
If this feature is enabled and the battery has
been installed over this period, there is a warn-
ing "Battery Age Alert" to indicate it.