5.2.2 Setup-Battery setting list
Table 5-5: Setup-Battery Setting list
Setting Item
Nominal Battery Voltage
Battery Capacity in Ah
Battery Groups
Maximum Charging Current
Battery Low/
Shutdown SETTING
Xtreme Power Conversion Corporation
Figure 5-24 Warning screen
Sub Item
--
--
--
Battery Low Voltage
Battery Low Capacity
Battery Shutdown Voltage
Uninterruptible Power Supply
Explanation
Set battery nominal voltage
8x12V (Default)
9x12V
10x12V
MUST be set after UPS installation
Set battery capacity.
7, 9 (Default), 10, 12, 17, 26, 40, 65, 100Ah
MUST be set after UPS installation or Battery
capacity is changed.
Set battery Groups
1 - default
Set battery maximum charging current (1~10)
4A (Default)
MUST be set after UPS installation or Battery
capacity is changed.
Set battery low voltage (10.5~11.5V)x(battery
Number)
11.2V x Battery Number (Default)
Set battery low capacity (20~50%)
20% (Default)
Set battery voltage point for system shutdown
in battery mode (10.0~11V) x (battery Number)
9.6V x Battery Number (Default)