NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Table of Contents IMPORTANT SAFETY INSTRUCTIONS: .......... 4 INTRODUCTION ................... 6 PRODUCT DESCRIPTION ................ 6 SYSTEM CONFIGURATION ................ 7 DETERMINING THE POWER REQUIREMENTS OF YOUR EQUIPMENT .................... 12 HARDWARE INSTALLATION GUIDE ........... 12 RACKMOUNT INSTALLATION STEPS .......... 19 INITIAL CONNECTION AND STARTUP: .......... 22 USER’S OPERATIONS ................ 24 TROUBLESHOOTING ................ 29 SPECIFICATIONS .................. 31 SHIPPING LIST .................. 34 OBTAINING SERVICE................ 35 ...
Page 3
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) EMC Statements ‐ FCC Part 15 Notice: Pursuant to section 15 of the FCC rules, this product has been tested and thereby complies to the conditions of a Class B (NXRT‐1000, NXRT‐1500) and Class A (NXRT‐2000, NXRT‐3000) digital device, which have been established for offering sufficient protection against dangerous interference for installation in a residential area. Installation and use of the equipment should comply with the instructions provided in order to avoid such interference due to the amount of radio frequency energy that is radiated and generated by the equipment. In spite of this, we cannot assure that a certain amount of interference may not occur in some installations. If, by turning on and off, it can be deduced ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) IMPORTANT SAFETY INSTRUCTIONS: (SAVE THESE INSTRUCTIONS) CAUTION! (UPS having Internal Batteries): Risk of electrical shock – Hazardous live parts inside this unit are energized from the battery supply even when the input AC power is disconnected. CAUTION! (No User serviceable Parts): Risk of electrical shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel. CAUTION! (Non‐isolated Battery supply): Risk of electric shock, battery circuit is not isolated from AC input, hazardous voltage may exist between battery terminals and ground. Test before touching. WARNING! (Fuses): To reduce the risk of fire, replace only with the same type and size of fuse. WARNING! Unit intended for installation in a controlled environment. CAUTION! Do not dispose of batteries in a fire, the battery may explode. CAUTION! Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes. CAUTION! A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries: ...
Page 5
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) CAUTION The unit has a dangerous amount of voltage. If the UPS indicator is on, the unit’s outlets may have a dangerous amount of voltage even when not plugged into the wall outlet because the battery may continue to supply power. Care should be taken to undertake installation indoors, free from electrically‐conductive particles which are under temperature and humidity control, in order to reduce the risk of electric shock. It is best to disconnect the device using the power supply cord. Ensure that the equipment is placed in a position near the outlet where easily accessible. Except for replacing the batteries, all servicing on this equipment must be carried out by qualified service personnel. ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) INTRODUCTION The information provided in this manual covers single phase 1000‐3000 VA uninterruptible power systems, their basic functions, operating procedures, options available and emergency situations. It also includes information on how to ship, store, handle, and install the equipment. Only detailed requirements of the UPS units are described herein, and installation must be carried out in accordance with this manual. Electrical installation must also carefully follow local legislation and regulations. Only qualified personnel should conduct these installations as failure to acknowledge electrical hazards could prove to be fatal. PRODUCT DESCRIPTION Many different kinds of sensitive electrical equipment can be protected by an Uninterruptible Power Supply (UPS) including computers, workstations, process control systems, telecommunications systems, ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Figure 1 – Block Diagram Diagnostic Tests When the UPS is started, a diagnostic test is automatically executed, checking the electronics and batteries, reporting any problems on the LCD display. A diagnostic test can also be performed manually from the front panel at any time. SYSTEM CONFIGURATION The UPS device and the internal batteries make up the system. Depending on the site and load requirements of the installation, certain additional options are available for the solution. Planning a UPS system, the following should be taken into consideration: ...
Page 9
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) LED Description The UPS has three LED’s on the front control panel. These LED’s allow the user to quickly understand if any action is needed. Red LED If this LED is illuminated it indicates a fault and the UPS will have no output. Faults that would indicate this alarm condition include: • Overload • Inverter fault • BUS fault • Over temperature fault [9] ...
Page 10
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Yellow LED If this LED is illuminated it indicates the user needs to take some action, and included: • UPS in Bypass Mode • Batteries Overcharged • Charger fault • Fan fault • Batteries discharged to low voltage level Green LED If this LED is illuminated it indicates that everything is normal and the UPS is being powered by incoming AC utility or by the batteries. LCD Descriptions There are four lines of information in the LCD display. Each line provides specific information related to the unit status and/or operation. Line information will be described from top to bottom with the top being line one. Line One Provides data in to numeric sections, with the data corresponding to the applicable category in line one and two Line Two Allows the user to identify which variable information is being displayed. ...
Page 11
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Line Four This indicates the status of the UPS. • ON LINE = utility mode • ON BATT = battery mode • ON BPS = bypass mode • UPS OFF = standby mode RS‐232 Standard Interface The RS‐232 interface uses a 9‐pin female D‐sub connector. Information provided includes data about utility, load and the UPS. The interface port pins and their functions are identified in the following table: PIN # FUNCTIONS 1,4,6,7,8 NOT USED 2 TRANSMIT 3 RECEIPT 5 GND 9 REMOTE WAKE UP CAUTION: MAX RATED VALUES 12VDC SNMP Communications Option The UPS provides an intelligent slot for internal or external network card. This special intelligent network card can be compatible with popular software and hardware found on the web and in operating systems. It can support operating systems such as HP Open View, IBM Netview, SUN Netmanager, etc. This enables the UPS to provide instant UPS and power information over the network. Please contact your reseller for additional details. Notes The UPS can be monitored through the RS232 interface or the SNMP card, but only one way at a time. The user can choose RS232 or SNMP communications through the communications switch on the rear panel of the UPS. RS232 is chosen if the switch is depressed to the RS232 position, and SNMP is chosen if the switch is depressed to the SNMP position. When there are two or more monitored pieces of equipment, the ground of each piece of equipment should be shared. The SNMP card is configured as DHCP by default IP setting. ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Remote Emergency Power Off (REPO) Port A customer supplied switch located remotely can be used to open the REPO connection and allows the UPS output receptacles to be switched off. Since the REPO shuts down the equipment immediately, orderly shutdown procedures are not followed by any power management software. The UPS will have to be manually restarted in order to regain power to the outlets on the UPS. DETERMINING THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1. Make sure the total Volt‐Amp (VA) requirements of your connected equipment does not exceed the maximum VA rating for the UPS. The maximum VA ratings are shown in the Specifications section of this document. 2. Ensure that the equipment plugged into the battery‐powered outlets does not exceed the UPS rated capacity. If UPS rated capacities are exceeded, an overload condition may occur and cause the UPS to shut down and trip the circuit breaker. 3. If the power requirements of your equipment are listed in values other than Volt‐Amps (VA), convert Watts (W) or Amps (A) into VA by doing the calculations below. Note: The equation below ...
Page 13
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Please handle the UPS and associated equipment with extreme caution since a high amount of energy is contained in the batteries. Always keep the unit in an upright position as marked on the packaging, and never drop the unit. Please adhere to the following instructions if the UPS is not installed immediately: • Store the equipment as is in its original packing and shipping carton. • Do not store in temperatures outside the range of ‐15°C to +25°C • Ensure that the equipment is fully protected from wet or damp areas and from moist air. In order to maintain the batteries, the UPS should be recharged every 6 months for at least 8 hours. If flammable substances such as gases or fumes are present, or if the room is airtight, a hazardous situation may exist in which no electrical equipment should be operated. The instructions in this manual explain how to install the UPS safely. Not acknowledging such electrical hazards may be fatal – keep this manual for future reference. WARNING! It is strongly recommended that the UPS cabinet not be opened as components have very high ...
Page 14
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Installation Standard brackets [14] ...
Page 21
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 6. 7. Note: Any external Battery Packs must be installed next to or under the UPS. Please refer to Appendix A: Battery Pack User Guide for more information when installing these. [21] ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) INITIAL CONNECTION AND STARTUP: Ensure that the UPS and optional battery packs are mounted correctly, and the UPS is disconnected from input power before proceeding. 1. Connect external battery packs (option) CAUTION: CONNECT ONLY BATTERY PACKS PROVIDING THE SAME DC VOLTAGE AS THE UPS – PLEASE DOUBLE CHECK LABELING ON THE UPS AND BATTERY PACKS TO ASSURE PROPER VOLTAGES ARE CONNECTED. CONNECTING THE INCORECT BATTERY PACK TO THE UPS MAY RESULT IN DAMAGE TO THE UPS AND/OR BATTERY PACK THAT WILL VOID THE WARRANTY. • Ensure that the UPS is disconnected from AC input and is off while connecting the External Battery Packs. Ensure all battery breakers are in the “OFF” position. ...
Page 23
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 6. Start and configure the UPS On/Off Button Function Button Inquiry Button • Press and hold the ON/OFF button for more than 3 seconds to turn on the UPS. The UPS should now start its inspection of the internal functions, main synchronization, and inverter startup. Then power should start to be supplied via the outlets. Once turned on, the UPS will perform a self‐test function, when the yellow LED turns to green, LCD displays “on line”, and means UPS is working in utility mode. ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) • NOTE: PLEASE VERIFY AUTOMATIC SHUTDOWN TIME PARAMETERS IN THE SETTINGS SECTION FOR YOUR SPECIFIC INSTALLATION. 9. After charging is complete, connect the loads to the UPS while monitoring the load levels via the UPS LCD or via the software. • Do not connect any devices that have the possibility of overloading the UPS. Refer to the Troubleshooting section and/or Technical Support with any problems during setup. USER’S OPERATIONS The only operations that users are permitted to do are: • Turning the UPS unit ON or OFF • Operating the user interfaces • Connecting data interface cables • Changing the batteries All such operations are to be performed exactly as instructed in this manual. The greatest care possible must be taken for any of these operations, and any change thereof may prove very hazardous to the operator. ...
Page 25
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) • Once turned on, the UPS will perform a self‐test function, when the yellow LED turns to green, LCD displays “On Batt” – the UPS is now functioning in DC mode. Turning Off the UPS when in DC Mode • Press and hold the ON/OFF button for more than 3 seconds to turn off the UPS. This means the internal inverter has been deactivated. • During the shutdown period, the UPS will run a self test. Once the self‐test has been completed, assuming there is still no AC input, the LCD will no longer display information. This indicates the UPS has no output. Self Test Operation Please refer to the three operating buttons on the front panel of the UPS. • Confirm the UPS is in “Utility Mode”. • Press and hold the “Function” button for a minimum of two seconds. • The self‐test will last for 10 seconds, during this time the LED’s will be lit in a sequential, repeating fashion. Audible Alarm silence in DC Mode or Fault Mode • When ...
Page 26
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) BATTERIES The life of batteries used in these UPS products is estimated at 3‐6 years depending on level of usage. Once the battery is no longer useful and must be replaced, please contact service personnel for assistance. REPLACING THE BATTERY (QUALIFIED SERVICE PERSONNEL ONLY) CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of Qualified Service Personnel knowledgeable of batteries and their precautions. CAUTION! Use only the specified type of battery. See your dealer for replacement batteries. CAUTION! The battery may present risk of electrical shock. Do not dispose of batteries in a fire as it may explode. Follow all local ordinances regarding proper disposal of batteries. ...
Page 27
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Slide the plastic cover to the right. Remover the M5x10 screws on the right side. Remove plastic front cover Locate the battery tray on the right front side of the UPS [27] ...
Page 28
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) Remove (4) M4x6 screws marked with letter A. Remove the battery tray from the UPS. [28] ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) TROUBLESHOOTING Audible Issue Alarm Description What You Should Do Alarm The “Input” Two Beeps Verify that utility voltage and letters in the per second The Input Voltage or frequency frequency is within acceptable second row at startup may be beyond the normal range. If so, contact support. of the LCD for 8 total acceptable range. are flashing seconds The “Input” Check wiring of input to UPS letters in the One beep Possible mis‐wiring AC line and (reversed wiring, etc) Rewire, if second row per 2 neutral line necessary of the LCD minutes are flashing Check UPS batteries. If necessary Battery ...
Page 30
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) LCD FAULT CODES BYP MODE LINE MODE BAT MODE BAT TEST MODE BUS FAULT 01 21 40 41 62 05 25 INV FAULT 61 63 04 24 42 OVERHEAT 33 06 08 43 OP SHORT / 16 02 44 OVERLOAD / 03 09 45 FAN FAULT 36 28 38 46 ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) SPECIFICATIONS 120V MODEL NXRT-1000 NXRT-1500 NXRT-2000 NXRT-3000 INPUT Voltage 120 VAC (80 - 138V at 100% load) 60-138V at 40% load Capacity VA (W) 1000 VA (700 W) 1500 VA (1050 W) 2000 VA (1400 W) 3000 VA (2100 W) Frequency 50/60 Hz auto sensing Power Factor...
Page 32
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 120V MODEL NXRT-1000 NXRT-1500 NXRT-2000 NXRT-3000 PHYSICAL Dimensions W x D x H (inches) W x D x H (inches) Unit Dimensions 17.3" x 17.7" x 3.4" 17.3" x 25.6" x 3.4" 17.3" x 21.7" x 5.2" Shipping Dimensions 22.3"...
Page 33
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) EXTENDED BATTERY NXRT-EBP1 NXRT-EBP2 NXRT-EBP3 PACK MODELS INPUT Voltage 120 VAC AC Current 1.5A 2.2A Frequency 50/60 Hz auto sensing Input Protection resettable circuit breaker CHARGER DC Voltage 41.2 ±0.5V 55.0 ±0.5V 110.0 ±0.5V OUTPUT DC Current 2.5A (max) Output Protection Fuse BATTERY...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) OBTAINING SERVICE If the UPS requires Service: 1. Use the TROUBLESHOOTING section in this manual to eliminate obvious causes. 2. Verify there are no circuit breakers tripped. 3. Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem, call Xtreme Power Conversion Corp Technical Support at 800.582.4524. Technical support inquires can also be made at support@xpcc.com. Please have the following information available BEFORE calling the Technical Support Department: a. Your name and address. b.
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) XTREME POWER CONVERSION™ (XPC) CORPORATION LIMITED WARRANTY Xtreme Power Conversion (XPC) Corporation warrants Xtreme Power Conversion equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship (excluding batteries) for a period of three years for NXRT‐Series products from the date of purchase. XPC ...
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) APPENDIX A: EXTENDED BATTERY PACK USER GUIDE Estimated Run Time for UPS with Extended Battery Packs LOAD RUNTIME FOR QTY OF EXTENDED BATTERY PACKS IN MIN. MODEL VA WATTS (1) EPB (2) EPB (3) EBP (4) EBP (5) EBP 500 350 333 NXRT‐ 1000 1000 700 170 750 525 447 NXRT‐ 1500 1500 1050 187 NXRT‐ 1000 700 737 2000 2000 1400 284 NXRT‐ 1500 1050 ...
Page 38
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) CAUTION : It is very critical to connect the correct voltage EBP with the UPS intended. EBP1 is for NXRT‐1000 EBP2 is for NXRT‐1500 EBP3 is for NXRT‐2000/3000 CONNECTING THE INCORRECT BATTERY PACK TO THE UPS MAY RESULT IN DAMAGE TO THE UPS AND/OR BATTERY PACK WILL VOID THE WARRANTY. All EBP’s have a different DC voltage configuration intended only for the UPS’s listed above. PLEASE DO NOT MIX EBP’s AND MAKE SURE YOU ONLY CONNECT THE EBP TO LIKE EBP’s OR UPS INDICATED ABOVE. DC VOLTAGES ARE MARKED ON BOTH THE UPS AND THE EBP – MAKE SURE THEY MATCH. [38] ...
Page 41
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) LED Description The Charging LED GREEN indicates that the battery charger in the Extended Battery Pack is charging normally with the AC power cord attached to the Battery pack. The Battery Test LED GREEN indicates that the DC output of the Extended Battery Pack (EBP) is normal. To perform the Battery Test, • switch the breaker on the rear of the EBP to ON position • press the Battery Test Button on the front panel of the EBP • the DC output from the EBP is normal when the Battery Test LED is illuminated Prior to connecting EBP’s, test each EBP to assure proper operation. Extended Battery Pack Operation The NXRT UPS System can be connected to multiple extended battery packs to increase the runtime when connected to the UPS supporting the load. Most UPS Systems are limited to one or two external ...
Page 42
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 2. The EBP’s use a cable shipped with each EBP to “daisy chain” together additional EBP’s to the first EBP being connected to the UPS in the appropriately labeled connector, or for connecting the first EBP to the UPS. 3. The AC input cord is for connecting AC utility to operate the Charger contained in each EBP. [42] ...
Page 43
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 4. The input AC Circuit Breaker will trip to the OFF position in the event that the internal EBP charger draws excessive current. Extended Battery Pack Installation CAUTION: Extended Battery Pack (EBP) Installation should be performed by qualified service personnel. 1. Verify that the DC circuit breaker on the rear panel of the EBP is in the OFF position. 2. Turn the UPS OFF and disconnect the UPS Input Cord from the AC wall outlet. 3.
Page 44
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 5. Secure the DC battery cable to both the rear of the UPS and the rear of the EBP by using M3 x 8 screws provided (2 each per connector end). 6. Repeat the above procedure for testing and securing each additional EBP required. CAUTION: Do not use extension cords when connecting input AC power to UPS or EBP’s 7. Move the DC circuit breaker on the rear of each EBP to the ON position. At this point the UPS will need to be started. 8. If the EBP’s are plugged into an AC source and properly installed, the internal batteries will be charged when acceptable voltage is present. EBP’s must be charged for a minimum of 6 hours for full battery time. NOTE: If the EBP is going to be out of service or stored for six months or longer, the batteries must be recharged for at least 36 hours every six months. Extended Battery Pack Q & A 1. Which EBP’s do I connect to an AC input source? • It is possible to plug in every EBP into an AC input source. The more connected the faster ...
Page 45
NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 5. Why don’t the LED’s on each EBP connected to an AC input source turn ON and OFF at the same time? • The charger on each EBP functions independently from the others. One EBP charger may be charging while another one might be at 100% and the charger turned off. This is normal operation of the EBP. [45] ...