ALPHABETIC REFERENCE
Internal parameters
I/O Dialog Box
Internal parameters
I/O Dialog Box
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Inputs
Three inputs where:
Register: number of register to be read (0 ...1023)
Reset: 1 = write value of input Value to register after reading
Value: reset value
Outputs
One output: Y = read value (=0 if register index is invalid)
None
NOTE:
Global registers are a block of 1024 values which can be read from or written to any
part of a control program. Whenever the controller is started, all registers will be
initialized with 0. Whenever the controller is stopped (e.g. in case of power failure),
all values will be lost. Registers cannot be accessed from outside using BACnet, an
engineering tool or the HTML interface.
Prerequisite
Controller OS 3.01.00 or higher
Function
Read the highest priority currently valid for the datapoint and returns it to the output.
If no priority is valid, the value 17 = relinquish default is transmitted.
Inputs
One input: DP
Outputs
One output: Prio
None
Prerequisite
Controller OS 3.02.00 or higher
Function
Read the selected priority of a datapoint. Other priorities set for this data point are
ignored.
Inputs
DP: datapoint to be read
Prio: priority (1..17) to be read (17 = relinquish default)

Read Priority Value (Excel Web II)

210
EXCEL CARE CONTROL ICONS

Read Priority (Excel Web II)